Innovative and sustainable cooling for FITLAB.
ITE College Central — passive displacement cooling for a 456 m² sports studies lab.
Baseline to verified result.
Baseline
A high-occupancy training space with demanding thermal comfort requirements, benchmarked against a conventional AHU and VAV configuration.
Engineering diagnosis
Conventional air distribution would over-supply the whole volume to condition the occupied zone, carrying a fan energy penalty for comfort nobody was in a position to feel.
YITAC scope
Twelve PDC coils sized for a 91.2 kW cooling load, with one primary AHU delivering 2,000 cmh of fresh air.
Verified result
Comfort maintained across the occupied zone with a materially lower connected load than the conventional comparison — measured, not modelled.
PDC system against conventional AHU + VAV.
| Category | PDC system | Conventional system |
|---|---|---|
| Power consumption | 0.5 kW | 7.5 kW |
| Annual energy (kWh) | 1,056 | 15,840 |
| Annual energy cost | $312 | $4,678 |